PENGALIHAN BEBAN OTOMATIS UNTUK TRAFO YANG TIDAK SEIMBANG BERBASIS LOGIKA FUZZY MAMDANY

Rangga Bismantara, Arief Marwanto

Abstract


Load imbalance in a three-phase distribution transformer can lead to increased neutral current and power losses, which negatively affect the efficiency and reliability of the power distribution system. This study aims to determine the level of load imbalance, the amount of power loss due to neutral current, and to evaluate the effectiveness of a two-time-point balancing method (WBP and LWBP) applied to transformer PNIAI007 at PT PLN (Persero) ULP Enarotali. In addition, a simulation using the Mamdani fuzzy logic method was conducted to validate the balancing results based on field measurement data.

 

The results show that the two-time-point balancing method significantly reduced load imbalance from 29% to 2.47% during the day and 1.21% at night. Neutral current decreased from 37.81 A to 14.58 A (daytime) and from 51.76 A to 19.83 A (night). Power losses were reduced by more than 85%. The Mamdani fuzzy simulation supported the accuracy of field data and can serve as a foundation for automatic load evaluation.


Keywords


load imbalance, neutral current, power loss, Mamdani fuzzy, power distribution

Full Text:

PDF PDF

References


D. F. Iman, P. Khaerunnisa, H. M. Fitri, dan D. Aribowo, “Analisis Operasional Sistem Distribusi Tegangan Menengah ke Tegangan Rendah di Gardu Induk Serang,” Journal of Electrical Power Control and Automation, vol. 7, no. 2, hlm. 66–71, 2024, doi: 10.33087/jepca.v7i2.119.

M. W. Siti, A. A. Jimoh, dan D. V. Nicolae, “Phase load balancing in the secondary distribution network using fuzzy logic,” dalam AFRICON 2007, 2007, hlm. 1–7. doi: 10.1109/AFRCON.2007.4401569.

N. V. Savina, Y. V. Myasoedov, dan L. A. Myasoedova, “Influence of Quality of the Electric Energy on Reliability of Electrical Supply Systems,” dalam 2018 International Multi-Conference on Industrial Engineering and Modern Technologies (FarEastCon), 2018, hlm. 1–5. doi: 10.1109/FarEastCon.2018.8602690.

P. C. Sekhar, R. A. Deshpande, dan V. Sankar, “Evaluation and improvement of reliability indices of electrical power distribution system,” dalam 2016 National Power Systems Conference (NPSC), 2016, hlm. 1–6. doi: 10.1109/NPSC.2016.7858838.

A. Azis dkk., “Analysis of Load Imbalance in Tarakan Distribution Transformer of PT PLN (Persero) Sukarami Customer Service Unit,” Maǧallaẗ Al-Handasaẗ Wa-al-Tiknūlūǧiyā, 2024, doi: 10.47191/etj/v9i05.12.

Sutikno, “Analisis Ketidakseimbangan Beban Transformator Distribusi 20 kV dan Solusinya pada Jaringan Tegangan Rendah,” Jurnal Teknik Elektro, vol. 8, no. 1, hlm. 1–7, 2018. [Daring]. Tersedia pada: https://ejournal.unesa.ac.id/index.php/JTE/article/view/26308

R. S. Widagdo dan A. H. Andriawan, “Analysis of Losses Due to Load Unbalance in a 2000 kVA Transformer at Supermall Mansion 2 Tower Tanglin Surabaya,” Journal of Engineering and Science Research, 2023, doi: 10.23960/jesr.v5i2.144.

S. Pranoto, Sofyan, dan N. N. Rusli, “Penyeimbangan Beban pada Trafo Distribusi Penyulang Akkarena di Unit Layanan Pelanggan Mattoanging PT PLN (Persero),” Jurnal Teknik Elektro, 2020.

M. H. Pratama dan Zainuddin, “Penyeimbangan Beban Gardu Distribusi dengan Metode Sehari Seimbang di Unit Layanan Pelanggan Mattoanging PT. PLN (Persero),” 2019.

A. D. Mulyadi, “Pengaruh Ketidakseimbangan Beban Pada Rugi Daya Saluran Netral Jaringan Distribusi Tegangan Rendah,” Jurnal Teknik Energi, 2011.

I. W. Y. Prasetya, I. N. Setiawan, dan I. G. D. Arjana, “Analisis Ketidakseimbangan Beban dan Harmonisa pada Transformator Distribusi MI 0096 Penyulang Abianbase,” Jurnal SPEKTRUM, vol. 7, no. 1, hlm. 109–115, 2020, doi: 10.24843/SPEKTRUM.2020.v07.i01.p16.

PT. PLN (Persero) UBSP3BJB, Pelatihan Operator Gardu Induk, Udiklat Semarang, 1985.

PT PLN (Persero), “Metode Pemeliharaan Trafo Distribusi Berbasis Kaidah Manajemen Aset,” 2014. [Daring]. Tersedia pada: https://id.scribd.com/document/348641264/1-SE-HAR-TRAFO-DIS-0017-E-tahun-2014-pdf

PT. PLN (Persero) ULP Enarotali, “Data – Data Internal dan Lapangan,” 2025.

E. S. Gil, J. E. M. Sivilla, A. S. González, dan Y. F. Cabrera, “Fuzzy logic applied to the diagnosis of technical conditions of distribution transformers,” Journal of Engineering and Applied Sciences, vol. 70, 2023, doi: 10.1186/s44147-023-00301-w.

C. R. Sarimuthu, V. K. Ramachandaramurthy, H. Mokhlis, dan K. R. Agileswari, “Comparison of Mamdani-Type and Sugeno-Type Fuzzy Inference Systems for Transformer Tap Changing System,” International Journal of Advances in Applied Sciences, vol. 5, no. 4, hlm. 163–167, 2016, doi: 10.11591/IJAAS.V5.I4.PP163-167.

R. F. Ningrum, R. R. A. Siregar, dan D. Rusjdi, “Fuzzy mamdani logic inference model in the loading of distribution substation transformer SCADA system,” IAES International Journal of Artificial Intelligence, vol. 10, no. 2, hlm. 298–305, 2021, doi: 10.11591/IJAI.V10.I2.PP298-305.

R. Prananda, H. S. Dini, dan T. W. O. Putri, “Design of Load Balancing Method on Secondary Distribution Network Using Artificial Intelligence Based on Fuzzy Logic,” dalam 2021 5th International Conference on High Voltage Engineering and Power Systems (ICHVEPS), 2021, doi: 10.1109/ICHVEPS53178.2021.9600977.

A. S. L. Dias dan I. G. Torné, “Automatic Balancing System of Single-Phase Consumer Units Connected to the Low-Voltage Distribution Network,” dalam Smart Energy and Advancement in Power Technologies, Springer, Cham, 2019, hlm. 97–111. doi: 10.1007/978-3-030-57548-9_9.

A. Ahmad dan M. S. Ali, “Automatic Load Sharing of Transformers Using Fuzzy Logic in a Distributed Generation Environment,” dalam 2023 IEEE REEDCON, 2023, hlm. 640–645. doi: 10.1109/REEDCON57544.2023.10151202.




DOI: https://doi.org/10.52447/jkte.v11i1.8475

Refbacks

  • There are currently no refbacks.